The breaker and wire sizes are selected based on the total amperage of the WarmlyYours heating system connected to a single thermostat. This information is on the WarmlyYours heating system's installation plan, electrical plan, or UL label. Based on guidelines from the National Electrical Code: loads up to 16 Amps may utilize 12 gauge wire with a 20-Amp breaker, and loads up to 12 Amps - 14 gauge wire with a 15-Amp breaker. Local code and/or other factors may change these guidelines.
Need more help? View support options
One thermostat can control multiple heating mats/cables as long as all the heating elements are using less than 15 amps:
TempZone™ will cover aprx. 120 sq. ft. for 120V systems and 240 sq. ft. for 240V systems on one thermostat.
Environ™ will cover aprx. 150 sq. ft. for 120V systems and 300 sq. ft. for 240V systems on one thermostat.
Slab Heat will cover aprx. 90 sq. ft. for 120V systems and 180 sq. ft. for 240V systems on one thermostat.
Need more help? View support options
Pressing and holding (2-3 sec) physical power/reset button will turn the unit completely OFF. Same process turns the unit back on.
(nHance and nJoin units will have the button on the front faceplate, nSpire Touch WiFi, nSpire Touch and nTrust will have the button on the right side of the faceplate.)
Need more help? View support options
You can control your slab heating system with any WarmlyYours nSpiration Series thermostat. Depending on the size of your project, you may also need to add a relay or nJoin power module.
Need more help? View support options
All thermostats are mandated at 42" height for handicap accessibility, most private residences are mounted at 52-60".
Please see this video on how to install a WarmlyYours nSpiration Series thermostat.
Need more help? View support options
Yes the adaptive function is reset during a factory reset.
Need more help? View support options
Check the connections between the thermostat and power module. If the power module is connected incorrectly to the thermostat, the power module won't switch off.
Need more help? View support options
No. The nJoin power module is not compatible with a Honeywell system.
Need more help? View support options
This indicates a fault, current to ground. The thermostat has cut off the power for your safety. Please contact your local electrician or WarmlyYours Technical Support.
Need more help? View support options
The ground wire in the floor mat must be connected directly to the ground wire of the supply or to the house ground wire.
Need more help? View support options
Approvals | cULus listed |
Ingress Protection (IPxx) Rating | IP21 |
Warranty | Limited 3-year warranty and lifetime technical support |
Connection | 4 wires, double pole |
Connection Method | Hardwired |
Ground Fault Protection | GFCI, Class A, 5 mA |
Maximum Current | 15 A |
Maximum Power | 1800 W @ 120 V, 3120 W @ 208 V, 3600 W @ 240 V |
Supply | 120 VAC, 208 VAC, 240 VAC (50/60Hz) |
Country of Origin (COO) | Denmark |
Depth | 2″ |
Installed Depth | 0.8125″ |
Length | 4.688″ |
Width | 2.875″ |
SKU | USG-4000 |