AIR-SS-2 Snow Owl sensor test with SCA-DUAL


Qualified-installer test values for a Snow Owl sensor connected to the SCA-DUAL / PD Pro.

This procedure is for a qualified installer using the SCA-DUAL / PD Pro manual. It involves powered measurements, and the heating system can activate during the test. Follow the manual’s electrical-safety and monitoring requirements; keep clear of line-voltage terminals and stop if smoke, an abnormal odor, or overheating occurs.

  1. Start with a clean, dry moisture-sensing grid.
  2. Measure DC voltage between the black and red sensor leads at the controller, with the meter’s negative lead on black. The manual specifies 23–28 VDC.
  3. With the sensor warm, above 38°F, and dry, measure between black and white. The expected reading is 22–28 VDC; SNOW and HEAT should be off.
  4. Cool the sensor temperature probe using the method in the manual. While the grid remains dry, SNOW and HEAT should remain off.
  5. Moisten the sensing grid. SNOW and HEAT should turn on, and white-to-black voltage should fall below 2 VDC.
  6. Allow the cold, moist sensor to warm above 38°F. SNOW should turn off, HEAT can remain on for hold-on time, and white-to-black voltage should return to 22–28 VDC.

Record results. After testing, disconnect power before restoring connections and covers, then restore the required hold-on setting. Do not transfer these voltage limits to an unrelated controller or sensor.