Cork flooring can be used with floor heating if the r-value is under 1. You will need to find the r-value of the flooring you choose and let your account manager know during the design stage. Cork flooring should have a low r-value to minimize trapped heat.
Reflective insulation is not effective with conductive heating, which is how embedded floor heating and snow-melting systems transfer heat. To be effective, the reflective insulation surface needs to face an air space (air gap), which allows the reflected heat to be redirected.
An effective solution considers the insulating material's R-Value. This is the rating of a material's insulating properties. The "R" stands for "resistance" and refers to the material's resistance to heat flow, or temperature conduction.
A Warmly Yours indoor floor heating system should not be installed with a GFCI breaker because GFCI protection is built into the thermostat and power module. And while it's not always required, we strongly recommend a dedicated circuit for each thermostat and power module to limit the occurrence of ground fault nuisance tripping caused by multiple GFCI devices on a circuit. The amperage of a breaker would depend on the amp draw of the heating system. For example, a TempZone Flex Roll (which provides approximately 15 watts of energy output per square foot) that is providing 15 square feet of heating coverage will draw only 225 watts ( 1.9 Amps), so a 15 Amp circuit would suffice. Always size breakers according to your local Electrical Code requirements.