PRO-Tect: Pipe Freeze Protection Economy Control with GFEP

PRO-Tect: Pipe Freeze Protection Economy Control with GFEP

Part Number: PT-ECONOMY
This support page provides publications, manuals, specifications, videos, support articles, and common support questions

Support Questions

Showing all 6 questions

Yes, you can extend the sensor up to 2,000 ft. cable for enhanced installation options

Was this helpful?

No, the FPT-130 (PT-Economy) is meant to be used with only the supplied thermistor sensor.

Was this helpful?
  • Hold down the red TEST/RESET pushbutton for approximately ten seconds.

      - After the first five seconds the unit will go into Manual Mode, energizing the heater cable if it is not all ready energized.

      – After the second five seconds the unit will enter the LOW TEMP blue LED edit mode. This is indicated by the blue LED flashing rapidly. Release the button at this point. (The unit will exit Manual Mode.). 

          Note: The blue LED may flash for a couple of seconds after releasing the red TEST/RESET pushbutton.

          • The blue LED will indicate whether the LOW TEMP Alarm is currently disabled or not.

                – If the blue LED remains on the LOW TEMP Alarm is currently enabled.

                – If the blue LED goes off the LOW TEMP Alarm is currently disabled.

                – To keep the setting as it is wait five seconds and the unit will resume normal operation.

                – To change this setting press the red TEST/RESET pushbutton within five seconds. The new status of this setting will show for three seconds before the unit resumes normal operation.

                     Note: The blue LED will flash rapidly before exiting the LOW TEMP blue LED editing mode and resuming normal operation.

          Was this helpful?

          The PT-ECONOMY controller (FTP 130) includes a Low Current Alarm feature. This alarm switches the system off if it detects a load current below 0.1 amps, unless Fire Protection Mode is enabled. The system checks the load current during each ground fault test and whenever the load is active. When connecting a load through a relay panel, Fire Protection Mode can be enabled to avoid the alarm.

          Was this helpful?
          • POWER indicator – This green LED lit solid indicates that the FPT 130 (PT Economy) is receiving power.

                – Blinking indicates a calibration error.

          • HEAT indicator – This yellow LED lit solid indicates when the heater is energized.

                – Blinking asymmetric (1/2 sec off × 1–1/2 sec on) : Low Current Alarm, heater relay closed.

                – Blinking asymmetric (1/2 sec on × 1–1/2 sec off) : Low Current Alarm, heater relay open.

                – Blinking fast : Stuck relay.

          • LOW TEMP indicator – This blue LED lit solid indicates when the temperature falls to 32 °F (0 °C) for all set-points except the 30 °F (-1.1 °C) set-point. For the 30 °F (-1.1 °C) set-point the LOW TEMP alarm will indicate when the temperature drops to 28 °F (-2.2 °C).

                – Blinking indicates sensor fault.

                – Blinking fast indicates High Temperature alarm.

          • ALARM indicator – This red LED lit solid indicates when there is a high ground fault current.

                – Blinking indicates a GFEP circuit failure (this light will also blink while system is performing a self–test).

          Was this helpful?

          The blue LED lit solid indicates when the temperature falls to 32 °F (0 °C) for all set-points except the 30 °F (-1.1 °C) set-point. For the 30 °F (-1.1 °C) set-point the LOW TEMP alarm will indicate when the temperature drops to 28 °F (-2.2 °C).

          Was this helpful?


          Specifications

          Electrical

          Activation Temperature 30 °F, 38 °F, 45 °F, 50 °F
          Connection Method Hardwired
          Ground Fault Equipment Protection (GFEP) Self-test GFEP 30mA
          Maximum Load (Resistive Only) 30 A
          Voltage 100 - 277 VAC

          Warranty / Certifications

          Approvals UL and CSA listed
          Area of Use Non-hazardous locations
          Ingress Protection (IPxx) Rating IP66
          Warranty 2 years
          Waterproofing NEMA 4X

          Product Dimensions

          Depth 4⅜″
          Height 5½″
          Installed Depth 0.75″
          Weight 3 lbs
          Width 8⅛″

          Identifiers

          SKU PT-ECONOMY
          UPC (GTIN-12) 881308057169