PT-ECONOMY Frequently Asked Questions

Don't see the answer you're looking for? Ask a question

Frequently Asked Questions

Showing 10 of 12 questions

No, the FPT 130 provides a summary alarm via a dry contact relay. This relay is energized whenever the unit is powered. So, with power off the NC contact is closed, and the NO contact is open. When the unit is powered these are in the opposite state. A fault will de-energize the alarm relay and close the NC contact. This allows for a default, power loss alarm without power.

Was this helpful?

No, the FPT-130 (PT-Economy) is meant to be used with only the supplied thermistor sensor.

Was this helpful?

Yes, you can extend the sensor up to 2,000 ft. cable for enhanced installation options

Was this helpful?
  • Hold down the red TEST/RESET pushbutton for approximately ten seconds.

      - After the first five seconds the unit will go into Manual Mode, energizing the heater cable if it is not all ready energized.

      – After the second five seconds the unit will enter the LOW TEMP blue LED edit mode. This is indicated by the blue LED flashing rapidly. Release the button at this point. (The unit will exit Manual Mode.). 

          Note: The blue LED may flash for a couple of seconds after releasing the red TEST/RESET pushbutton.

          • The blue LED will indicate whether the LOW TEMP Alarm is currently disabled or not.

                – If the blue LED remains on the LOW TEMP Alarm is currently enabled.

                – If the blue LED goes off the LOW TEMP Alarm is currently disabled.

                – To keep the setting as it is wait five seconds and the unit will resume normal operation.

                – To change this setting press the red TEST/RESET pushbutton within five seconds. The new status of this setting will show for three seconds before the unit resumes normal operation.

                     Note: The blue LED will flash rapidly before exiting the LOW TEMP blue LED editing mode and resuming normal operation.

          Was this helpful?
          • POWER indicator – This green LED lit solid indicates that the FPT 130 (PT Economy) is receiving power.

                – Blinking indicates a calibration error.

          • HEAT indicator – This yellow LED lit solid indicates when the heater is energized.

                – Blinking asymmetric (1/2 sec off × 1–1/2 sec on) : Low Current Alarm, heater relay closed.

                – Blinking asymmetric (1/2 sec on × 1–1/2 sec off) : Low Current Alarm, heater relay open.

                – Blinking fast : Stuck relay.

          • LOW TEMP indicator – This blue LED lit solid indicates when the temperature falls to 32 °F (0 °C) for all set-points except the 30 °F (-1.1 °C) set-point. For the 30 °F (-1.1 °C) set-point the LOW TEMP alarm will indicate when the temperature drops to 28 °F (-2.2 °C).

                – Blinking indicates sensor fault.

                – Blinking fast indicates High Temperature alarm.

          • ALARM indicator – This red LED lit solid indicates when there is a high ground fault current.

                – Blinking indicates a GFEP circuit failure (this light will also blink while system is performing a self–test).

          Was this helpful?

          The blue LED lit solid indicates when the temperature falls to 32 °F (0 °C) for all set-points except the 30 °F (-1.1 °C) set-point. For the 30 °F (-1.1 °C) set-point the LOW TEMP alarm will indicate when the temperature drops to 28 °F (-2.2 °C).

          Was this helpful?

          At a minimum: a PRO-Tect Pipe Freeze Protection Self-Regulating Cable, an End Seal kit, and a Power Connection Kit. However, we also strongly recommend a control. All of these components are directly available from WarmlyYours (along with other accessories).

          Use of another manufacturer’s components will void the warranty.

          Was this helpful?

          WarmlyYours offers four thermostat and controller options for PRO-Tect pipe freeze protection heating systems:

          • Air Sensing Thermostat (AIR-STAT) — A simple automatic thermostat with a capillary bulb sensor. Activates when air temperature drops to 40°F and shuts off when it warms back up. Lowest-cost automatic option. Rated for 22A at 240V. NEMA 4X outdoor enclosure.
          • Economy Pipe Thermostat (PT-ECONOMY) — Four fixed temperature setpoints (30°F, 38°F, 45°F, 50°F), built-in GFEP, LED status indicators, and a 20-foot sensor lead. Rated for 30A. Good for standard residential and light commercial installations.
          • Single-Zone Digital Thermostat (PT-SINGLE) — Fully adjustable setpoint (-99.9°F to 999°F) with a 2.7" display, adjustable GFEP (1–300mA), and a 100k ohm NTC sensor with 20-foot lead. Rated for 30A. Best for precise temperature control.
          • Dual-Zone Digital Thermostat (PT-DUAL) — Same digital control as the PT-SINGLE but manages two independent heating circuits from a single enclosure. Includes two sensors. Best for large installations or multi-zone pipe protection.

          All controls include the sensor, feature NEMA 4X weatherproof enclosures, and are rated for non-hazardous locations. Contact our radiant experts for help selecting the right control for your project.

          Was this helpful?

          GFEP stands for Ground Fault Equipment Protection. It is a safety circuit that continuously monitors the current flowing through your heating cable. If a ground fault is detected (current leaking to ground, which can indicate damaged cable insulation), the GFEP trips the circuit and shuts the system off.

          GFEP is important for pipe freeze protection systems because:

          • Heating cables are often installed in damp or wet environments (under pipes, in crawl spaces) where insulation damage is more likely.
          • A ground fault in a high-current heating circuit can cause fire, shock hazard, or cable failure.
          • GFEP trips before the fault escalates, protecting your property and your heating system.

          The PT-ECONOMY includes a fixed 30mA GFEP. The PT-SINGLE and PT-DUAL have adjustable GFEP (1–300mA) so you can set a sensitivity level appropriate for your installation. The AIR-STAT does not include GFEP.

          If your installation is in a wet or damp location, WarmlyYours recommends choosing a control with built-in GFEP for maximum protection.

          Was this helpful?

          The correct temperature setpoint depends on which control you have and where the sensor is installed:

          Air Sensing Thermostat (AIR-STAT) — Fixed setpoint of 40°F. The system activates when air temperature drops to this level and shuts off when it warms up. No adjustment needed.

          Economy Thermostat (PT-ECONOMY) — Four preset options: 30°F, 38°F, 45°F, or 50°F. For most pipe freeze protection applications, 38°F or 40°F is a good starting point—it activates the cable before pipes reach freezing temperatures.

          Digital Thermostats (PT-SINGLE / PT-DUAL) — Fully adjustable. A common recommendation is to set the activation point between 35°F and 40°F if measuring air temperature near the pipes, or slightly higher (45°F–50°F) if the sensor is measuring pipe surface temperature directly.

          For specific guidance on setpoint and sensor placement for your installation, contact our radiant experts—we can help you set up the system correctly for your climate and pipe location.

          Was this helpful?

          You need the PT-DUAL dual-zone thermostat when your pipe freeze protection installation has two independent heating circuits that you want to control from a single enclosure.

          Common scenarios that require dual-zone control:

          • Two separate pipe runs in different areas (e.g. crawl space and exposed exterior plumbing)
          • A large installation that was split across two circuits to stay within the 30A per-circuit load limit
          • Two different pipe materials or exposure levels that benefit from independent temperature setpoints

          The PT-DUAL includes two sensors and two independent sets of controls in one NEMA 4X enclosure. Each zone can have its own temperature setpoint and operates independently.

          If you only have one heating circuit, the PT-SINGLE is sufficient. If you are unsure how many circuits your installation requires, our free system design service will tell you exactly what you need.

          Was this helpful?

          Turn on heat tape when temperatures drop to 20°F (-6°C) or below and are expected to stay there for 6+ hours. For optimal protection, use automatic controls that activate cables based on temperature conditions.Manual operation:

          • Turn on: When temps forecast to reach 20°F or below for extended periods
          • Turn off: When temps rise above 40°F and stay there for 24+ hours
          • Monitor: Check daily during cold snaps

          Automatic operation (recommended):

          • Thermostat control: Activates at preset temperature (typically 32–40°F)
          • Smart control: Remote monitoring and weather-based activation
          • Timer control: Set schedule for coldest overnight hours

          Optimal operating temperatures:

          • Below 20°F: Peak freezing risk (heat tape should run continuously)
          • 20–32°F: Moderate risk (run heat tape, especially overnight)
          • Above 32°F: Lower risk, but vulnerable pipes may still need protection

          Operating tips:

          • Start early: Turn on heat tape before temperatures drop for best results
          • Run overnight: Pipes freeze most often during coldest overnight hours
          • Extend runtime: Keep heat tape on until temps stay above 40°F for 24+ hours
          • Don't turn off too early: Pipes can freeze during brief cold snaps

          When to activate by region:

          • Northern climates: October–April (extended winter season)
          • Moderate climates: November–March (core winter months)
          • Southern climates: December–February (occasional freezes)

          Energy-saving tip: Smart controls can reduce operating costs by 30–50% by running cables only when needed. They monitor weather forecasts and activate automatically. Shop control options.

          Emergency activation: If you forgot to turn on heat tape and temps drop suddenly, activate immediately and let water drip from faucets until pipes warm up.

          Was this helpful?