SCA-DUAL Frequently Asked Questions

Don't see the answer you're looking for? Post your question

Frequently Asked Questions

Showing all 6 questions

The AIR-SS-2 can be mounted at a distance up to 500 feet away from the controller using 22-gauge wires and up to 1000 feet using 18-gauge wires.

Was this helpful? Yes No

GFEP is the National Electric Code (NEC) required protection for fixed outdoor deicing and snow-melting equipment, which may be accomplished by using circuit breakers equipped with ground-fault equipment protection (GFEP) of 30 mA. It is important to understand that this required equipment protection is NOT the same as a 5 mA GFCI used for personal protection.

11 people found this helpful Was this helpful? Yes No

When the design requirement's amp draw exceeds the selected controller's capacity.

5 people found this helpful Was this helpful? Yes No

It depends on how the system is intended to operate. If the expectation is manual operation (ex. WiFi or Timer Control), then no sensors are required. If the expectation is automatic operation, then the system will require at least one snow sensor.

2 people found this helpful Was this helpful? Yes No

Ground fault equipment protection (GFEP) is intended to provide protection for equipment against damaging line-to-ground currents by disconnecting all ungrounded conductors of the faulted circuit.

2 people found this helpful Was this helpful? Yes No

No, a sensor is not required with the snow melt system. However, certain automatic controllers require a temperature/moisture sensor to sense atmospheric conditions and may also require an in-slab, high temperature limit sensor to be installed (notably, asphalt installations).

1 person found this helpful Was this helpful? Yes No