The PT-ECONOMY is a relatively affordable pipe freeze protection control for most commercial applications and residential applications. It comes with four manually adjustable temperature set points: 30, 38, 45, and 50 degrees Fahrenheit. It comes with a built-in relay (capable of handling up to 30 amps), a 20-ft. sensor, and Ground Fault Equipment Protection (GFEP). This control can be installed outdoors (NEMA 4X rated waterproofing). Works with voltages ranging from 100-277 VAC.
| Activation Temperature | 30 °F, 38 °F, 45 °F, 50 °F |
| Connection Method | Hardwired |
| Ground Fault Equipment Protection (GFEP) | Self-test GFEP 30mA |
| Maximum Load (Resistive Only) | 30 A |
| Voltage | 100 - 277 VAC |
| Approvals | UL and CSA listed |
| Area of Use | Non-hazardous locations |
| Ingress Protection (IPxx) Rating | IP66 |
| Warranty | 2 years |
| Waterproofing | NEMA 4X |
| Depth | 4⅜″ |
| Height | 5½″ |
| Installed Depth | 0.75″ |
| Weight | 3 lbs |
| Width | 8⅛″ |
| SKU | PT-ECONOMY |
| UPC (GTIN-12) | 881308057169 |
Showing all 5 questions
No, the FPT 130 provides a summary alarm via a dry contact relay. This relay is energized whenever the unit is powered. So, with power off the NC contact is closed, and the NO contact is open. When the unit is powered these are in the opposite state. A fault will de-energize the alarm relay and close the NC contact. This allows for a default, power loss alarm without power.
No, the FPT-130 (PT-Economy) is meant to be used with only the supplied thermistor sensor.
Yes, you can extend the sensor up to 2,000 ft. cable for enhanced installation options
- After the first five seconds the unit will go into Manual Mode, energizing the heater cable if it is not all ready energized.
– After the second five seconds the unit will enter the LOW TEMP blue LED edit mode. This is indicated by the blue LED flashing rapidly. Release the button at this point. (The unit will exit Manual Mode.).
Note: The blue LED may flash for a couple of seconds after releasing the red TEST/RESET pushbutton.
– If the blue LED remains on the LOW TEMP Alarm is currently enabled.
– If the blue LED goes off the LOW TEMP Alarm is currently disabled.
– To keep the setting as it is wait five seconds and the unit will resume normal operation.
– To change this setting press the red TEST/RESET pushbutton within five seconds. The new status of this setting will show for three seconds before the unit resumes normal operation.
Note: The blue LED will flash rapidly before exiting the LOW TEMP blue LED editing mode and resuming normal operation.
– Blinking indicates a calibration error.
– Blinking asymmetric (1/2 sec off × 1–1/2 sec on) : Low Current Alarm, heater relay closed.
– Blinking asymmetric (1/2 sec on × 1–1/2 sec off) : Low Current Alarm, heater relay open.
– Blinking fast : Stuck relay.
– Blinking indicates sensor fault.
– Blinking fast indicates High Temperature alarm.
– Blinking indicates a GFEP circuit failure (this light will also blink while system is performing a self–test).