Nonprogrammable Thermostat with 15 mA EGFPD (ATN4-4999)

Nonprogrammable Thermostat with 15 mA EGFPD (ATN4-4999)

Part Number: ATN4-4999Past Model
The nTrust Non Programmable Thermostat with built-in GFCI provides optimal comfort in controlling electrical underfloor heating - all with a stylish design.
This support page provides publications, manuals, specifications, videos, support articles, and common support questions

Support Questions

Showing 10 of 22 questions

The breaker and wire sizes are selected based on the total amperage of the WarmlyYours heating system connected to a single thermostat. This information is on the WarmlyYours heating system's installation plan, electrical plan, or UL label. Based on guidelines from the National Electrical Code: loads up to 16 Amps may utilize 12 gauge wire with a 20-Amp breaker, and loads up to 12 Amps - 14 gauge wire with a 15-Amp breaker. Local code and/or other factors may change these guidelines.

6 people found this helpful Was this helpful? Yes No

One thermostat can control multiple heating mats/cables as long as all the heating elements are using less than 15 amps:

TempZone™ will cover aprx. 120 sq. ft. for 120V systems and 240 sq. ft. for 240V systems on one thermostat.

Environ™ will cover aprx. 150 sq. ft. for 120V systems and 300 sq. ft. for 240V systems on one thermostat.

Slab Heat will cover aprx. 90 sq. ft. for 120V systems and 180 sq. ft. for 240V systems on one thermostat.

5 people found this helpful Was this helpful? Yes No

In theory, it is possible, if no other options are available. We do not recommend it, but If the thermostat is controlling the floor temperature with a floor sensor, then it can go on an exterior wall. It is important that the floor sensor gets located in an area of the floor not hit by sunshine.

If the thermostat will be controlling the air temperature with the built-in ambient sensor, then it should go on an interior wall.

3 people found this helpful Was this helpful? Yes No

A GFCI/GFEP (Ground Fault Circuit Interrupter / Ground Fault Equipment Protection) works differently than a circuit breaker by specifically detecting a small imbalance in electrical current between the hot and neutral wires, which indicates a potential ground fault (like a person touching a live wire), and instantly shutting off the power to prevent shock, while a circuit breaker only trips when there's a significant overload in current flow on the circuit, like a short circuit or too many appliances plugged in.

3 people found this helpful Was this helpful? Yes No

Pressing and holding (2-3 sec) physical power/reset button will turn the unit completely OFF. Same process turns the unit back on.

(nHance and nJoin units will have the button on the front faceplate, nSpire Touch WiFi, nSpire Touch and nTrust will have the button on the right side of the faceplate.)

2 people found this helpful Was this helpful? Yes No

The ground wire in the floor mat must be connected directly to the ground wire of the supply or to the house ground wire.

2 people found this helpful Was this helpful? Yes No

Relays can fail due to excessive current or voltage. When a relay is exposed to too much current, the contacts can burn out. High voltage can also damage the coil. Other reasons include mechanical wear and tear, dust or dirt buildup, and moisture. These factors can cause the relay to malfunction or stop working entirely. Regular maintenance and using the relay within its specified limits can help prevent failures.

2 people found this helpful Was this helpful? Yes No

Yes, the sensor wires may be trimmed.  Most local code requirements call for 6“-7“ of extra wire from the gang box.

1 person found this helpful Was this helpful? Yes No

Check the connections between the thermostat and power module. If the power module is connected incorrectly to the thermostat, the power module won't switch off.

USG Power Module Connection Diagram


1 person found this helpful Was this helpful? Yes No

82°F - 85°F is the most common comfortable warm temperature of the floor.

1 person found this helpful Was this helpful? Yes No

Our thermostats are indoor rated. So long as they are kept within normal indoor humidity levels, they will continue to operate optimally. These thermostats are not rated to be installed in wet areas, steam rooms, or rooms with abnormal humidity levels or poor ventilation.

Was this helpful? Yes No
Was this helpful? Yes No

The flashing digits indicate that the actual (measured) floor temperature exceeds the thermostat temperature limit.

The temperature limit is set for either tile (104°F/40°C) or laminate (82°F/28°C) when the thermostat is first set up or re-configured.

For example: When the floor type (protection) is set to laminate, the limit defaults to 82°F/28°C. If the floor temperature goes above this - whether due to radiant floor heating or external heating sources, then the digits will flash and the heating is switched off.

Turning the temperature up or down will not affect the flashing digits. And leaving the thermostat alone with flashing digits does not harm the system.

Tip: To turn off the heated floor (ex. for months when it is not needed), on the outer edge of the thermostat, depress the lower right side button for 3-5 seconds. This will also turn it back on.

Was this helpful? Yes No

All thermostats are mandated at 42" height for handicap accessibility, most private residences are mounted at 52-60".

Please see this video on how to install a WarmlyYours nSpiration Series thermostat.

Was this helpful? Yes No

Yes, the floor sensor wire can be extended up to 300 feet with 18 AWG wire.

Was this helpful? Yes No

Turn the power (circuit breaker typically) to the thermostat off for 5 minutes and then back on to reset the thermostat.

If there is power to the thermostat and it still doesn't appear to work, then the next step toward a solution is to take Ohm measurements of the floor heating system.

This is done with a digital multi-meter that can select a low 200 Ohm (Ω) scale. To conduct this test, turn off the circuit breaker. Remove the thermostat completely from the wall and disconnect the wires connected to the LOAD connections at the back of the thermostat. Disconnect the ground wires from the house ground, and do the test shown on the links below. If you are uncomfortable doing this test, contact a qualified electrician.

Please follow one of these guides based on the type of heating system installed:

TempZone Single Conductor

TempZone Twin Conductor

For a quick overview of the testing process:

Here is a video showing how the test is done

Here is a video showing how to locate and identify the floor heating wires

If the system still does not function, contact +1 (800) 875-5285 WarmlyYours Technical Support and provide the Ohm measurements for further assistance.

Was this helpful? Yes No

This indicates a fault, current to ground. The thermostat has cut off the power for your safety. Please contact your local electrician or WarmlyYours Technical Support.

Was this helpful? Yes No

That is the sound the thermostat makes when the relay is either opened or closed to turn on or off the power to the floor heating elements. See this article for further information.

Was this helpful? Yes No

WarmlyYours controllers incorporate built-in Class A GFCI protection for all new floor heating systems.  Class A GFCI provides personnel protection and trips when ground fault current exceeds 5 mA (milliamps).  Class B GFCI protection is pretty much obsolete, but older systems may still require it.  WarmlyYours controllers with built-in Class B GFCI provide equipment and circuit protection and operates when a fault to ground exceeds 15 mA.

Was this helpful? Yes No

For systems below 12 Amps, a 15 Amp, Non-GFI breaker is fine. For systems 12 to 16 Amps, a 20 Amp, non-GFI breaker is needed. Breaker sizes are noted on the installation plan that ships with many orders.

Was this helpful? Yes No

GFCI can fail for various reasons, such as wear and tear, moisture, corrosion, power surges, faulty wiring, or improper installation. Some of these causes can be prevented by regular inspection and maintenance, while others may require professional assistance. It is important to note that GFCI devices (ex. thermostat, breakers, outlets) should be tested regularly as these do wear out over time.

Was this helpful? Yes No

A floor sensor measures floor temperature so a compatible thermostat can regulate comfort and enforce the flooring manufacturer’s temperature limit. Some thermostats, including nTrust 2.0, offer a regulator mode without a sensor, but that mode does not measure floor temperature. Use sensor-based temperature control whenever required by the flooring or heating-system instructions.

Was this helpful? Yes No


Specifications

Warranty / Certifications

Approvals cULus listed
Warranty Limited 3-year warranty and lifetime technical support

Electrical

Connection 4 wires, double pole
Connection Method Hardwired
Ground Fault Protection 15mA EGFPD
Maximum Current 15 A
Maximum Power 1800 W @ 120 V, 3120 W @ 208 V, 3600 W @ 240 V
Supply 120 VAC, 50/60Hz / 240 VAC, 50/60Hz

Product Dimensions

Depth 2″
Installed Depth 0.75″
Length 5⅛″
Weight 0.75 lbs
Width 3¼″

Controls

Display Backlit Display
Display Size 2.5″

Thermostat

Floor Sensor Compatibility 10k ohms only
Includes Floor Sensor Yes (1)
Maximum Ambient Temperature Setting 77 °F
Maximum Floor Temperature Setting 104 °F
Minimum Ambient Temperature Setting 32 °F
Minimum Floor Temperature Setting 41 °F
Programmable No